Thermal/Temperature Monitoring/Camera Configuration

Revision as of 19:16, 5 May 2020 by Marques.Phillips (talk | contribs)

(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

Temperature Monitoring Solution Camera Configuration

This guide will cover the camera Configuration for the Thermal Temperature Monitoring Solution

TPC Configuration Flow.png

Check latest firmware and upgrade

Open smart thermal of human body temperature measurement

==Set Smart Thermal Plan==


Enable the Smart Thermal Smart Plan for the Thermal Camera

  • Log into Camera

Click Setting

Temperature Monitoring - Camera Configuration - 1.jpg

Click Smart Thermal > Smart Plan

Temperature Monitoring - Camera Configuration - 2.jpg

Click the Smart thermal icon.jpg icon to enable the plan.

Click Save

Temperature Monitoring - Camera Configuration - 3.jpg

Set rules of human temperature measurement

Set Rules Of Human Temperature Measurement

Configure the parameters for the Human Temperature Measurement

  • Log into Camera

Click Setting

Temperature Monitoring - Camera Configuration - 1.jpg

Click Smart Thermal > Thermal Temperature Monitoring

Temperature Monitoring - Camera Configuration - 4.jpg

Check the box to enable human temperature measurement

Temperature Monitoring - Camera Configuration - 5.jpg

Check the box to enable Temperature report - this will report/display all temperature values

Temperature Monitoring - Camera Configuration - 6.jpg

Check the box to enable High Temperature Warning - an alarm will be sent when the temperature is higher than or equal to this value

Temperature Monitoring - Camera Configuration - 7.jpg

Click Draw Rule to configure the rule box

Temperature Monitoring - Camera Configuration - 8.jpg

Left click inside the frame to draw the box

Temperature Monitoring - Camera Configuration - 9.jpg

Completed

Temperature Monitoring - Camera Configuration - 10.jpg

Click Save

Temperature Monitoring - Camera Configuration - 11.jpg

Set blackbody parameters

Set Blackbody Parameters

Configure the parameters for the Blackbody device for Human Temperature Measurement

  • Log into Camera

Click Setting

Temperature Monitoring - Camera Configuration - 1.jpg

Click Smart Thermal > Thermal Temperature

Select the Blackbody parameter tab

Temperature Monitoring - Camera Configuration - 12.jpg

Check the box to enable

Temperature Monitoring - Camera Configuration - 13.jpg

Click inside the video frame to select the green rule box

The rule needs to be drawn along the bold highlighted edge, just surrounding the highlighted area of the blackbody

Temperature Monitoring - Camera Configuration - 14.jpg

Left click to drag and move the box and click the corners to resize the box

Temperature Monitoring - Camera Configuration - 15.jpg

Click Save

Temperature Monitoring - Camera Configuration - 16.jpg

Example of properly configured Blackbody box:

Blackbody complete setup.png]

Configure Advanced/Other Settings

Configure Advanced/Other Settings

Configure advanced/other parameters for the camera for Human Temperature Measurement

  • Log into Camera

Click Setting

Temperature Monitoring - Camera Configuration - 1.jpg

Click Smart Thermal > Thermal Temperature

Click the Smart Channel tab

Select which channel is used for Intelligent analysis

For normal scenes Visual channel is used to detect faces by default

For some scenes such as dark or with backlight environment, Thermal channel can be used

Snap Angle Filter - larger the value, easier it is to capture the side face

For example , when value is 1 , only the front face can be detected

Temperature Monitoring - Camera Configuration - 17.jpg

Click Save

Check environment temperature

Check Environment Temperature

If the default temperature parameters are not accurate this situation will affect the human body temperature measurement.

If human body temperature is inaccurate, try the following steps:

Step 1 - Ambient temperature

  • Log into Camera
    • Setting > Smart Thermal > Human temperature measurement > Others

Temperature Monitoring - Camera Configuration - 19.jpg

  • Use thermometer to detect the real ambient temperature on site and enter the number

Temperature Monitoring - Camera Configuration - 21.jpg

Temperature Monitoring - Camera Configuration - 22.jpg

  • Click Save

Step 2 - Human temperature correction

  • Use a thermometer to detect the real Human body temperature:

Thermometer.JPG

Calculate the difference between real Human body temperature and measure the temperature from the thermal camera, enter this value in Human Temperature correction field.

Smart Thermal > Human Temperature Monitoring > Blackbody parameter:

Temperature Monitoring - Camera Configuration - 24.jpg

For example: real Human body temperature is 98.6F (37C), measure temperature in thermal camera is 100F (37.8C)

Human Temperature correction should be 98.6 - 100 = -1.4

Click Save

Event Verification

Event Verification

Once configuration is complete, go to Live interface to verify temperature measurement

  • Log into Camera
  • Check measurement value on screen

Temperature Monitoring - Camera Configuration - 23.jpg

    • Compare it with the value on the frontal temperature gun, thermometer ( if available)